Methodology and References
This page documents how Conduit Calculator Pro performs its current calculations and identifies the sources used for engineering reference data.
Calculation method
- The area of each round cable is calculated as π × (outside diameter ÷ 2)².
- Cable area is multiplied by quantity, then combined across all cable entries.
- Permitted conduit area is calculated as conduit internal area × selected fill percentage.
- The result passes when combined cable area is less than or equal to permitted conduit area.
Calculations use inches and square inches internally. Metric displays are conversions from those internal values.
For identical cables in Automatic electrical fill mode, the maximum whole-cable quantity follows Chapter 9, Table 1, Note 7: a calculated fractional result of 0.8 or greater permits rounding to the next whole cable. The calculator identifies this qualified outcome as PASS — NEC ALLOWANCE and separately shows that the direct area comparison exceeds the displayed fill percentage. Planning fill modes do not use this allowance.
Voltage-drop calculation method
The Voltage Drop Calculator uses the entered one-way distance from source to load. DC two-wire and single-phase circuits use a circuit factor of 2; balanced three-phase circuits use √3.
- DC two-wire: voltage drop = 2 × current × one-way length × conductor resistance.
- Single-phase AC: voltage drop = 2 × current × one-way length × effective impedance.
- Balanced three-phase AC: voltage drop = √3 × current × one-way length × effective impedance.
- AC effective impedance = resistance × power factor + reactance × sin(arccos(power factor)).
Resistance is modeled as resistivity divided by conductor area. The calculator uses 75°C resistivity values of 0.0225 Ω·mm²/m for copper and 0.036 Ω·mm²/m for aluminum. AWG areas are generated from the standard AWG geometric relationship; kcmil areas are converted from circular mils. When project-specific AC reactance is unavailable, the interface defaults to 0.08 mΩ/m and makes that assumption editable.
When a temperature other than 75°C is selected, resistance is adjusted linearly using a temperature coefficient of 0.00393/°C for copper or 0.00403/°C for aluminum. Parallel conductors are modeled as identical, equal-length paths that share current equally, so the modeled resistance and reactance are divided by the number of parallel conductors per phase or polarity. Real installations must still satisfy all parallel-conductor and current-sharing requirements.
For load conversion, amperes are used directly. Single-phase watts are divided by voltage and power factor; balanced three-phase watts are divided by √3 × line-to-line voltage × power factor. VA and kVA are apparent-power inputs, so they are divided by voltage and the applicable phase factor without another power-factor adjustment. DC watts are divided by DC voltage.
In feeder-plus-branch mode, each segment is calculated independently using its one-way length and conductor. The segment voltage drops are added, and the combined percentage is referenced to the original source voltage. The final load voltage is source voltage minus both segment drops.
These equations and assumptions follow Eaton's published voltage-drop guidance and are consistent with the inputs presented by Southwire's published voltage-drop calculator. See the Eaton Bussmann electrical formulas handbook and Southwire voltage-drop calculator.
The selected voltage-drop target is a design input. A 3% target is common, and NEC informational notes discuss 3% branch-circuit and 5% combined feeder-plus-branch performance, but that context is not a universal mandatory conductor-sizing rule. Confirm the adopted code and project requirements. Most importantly, the calculator's minimum-size recommendation is based on voltage drop only and does not verify ampacity, continuous loads, adjustment factors, terminal ratings, overcurrent protection, or fault current.
See the voltage-drop instructions or open the Voltage Drop Calculator.
Branch-circuit coordination method
The Branch Circuit Wire Size Calculator composes the same calculation engines used by Wire Ampacity, Voltage Drop, and Equipment Grounding Conductor. It does not maintain a separate set of electrical tables.
- Find the first supported conductor whose corrected, adjusted, terminal-limited, and small-conductor planning ampacity meets noncontinuous load plus 125% of continuous load.
- Evaluate the actual operating load across each supported conductor and find the first size meeting the entered voltage-drop target.
- Select the first conductor satisfying the load, voltage-drop target, and user-confirmed protective-device rating.
- Use that installed conductor, the ampacity minimum, and the confirmed protective device in the supported wire-type equipment-grounding calculation.
- Transfer the circuit conductors and EGC to Conduit Size, where exact published conductor products must be selected before conduit fill is calculated.
This scoped workflow excludes neutral determination, parallel conductors, motors, HVAC, welders, EV-specific provisions, taps, dwelling allowances, hazardous locations, fault-current verification, and complete code compliance.
Ampacity and derating method
The Wire Ampacity Calculator is intentionally limited to a common 2023 NEC Table 310.16 pathway for insulated conductors rated 0–2000 volts in raceway, cable, or earth. The table basis is not more than three current-carrying conductors and 30°C ambient.
Ambient temperature may be entered in Celsius or Fahrenheit. The interface shows the equivalent value and converts Fahrenheit to Celsius before selecting the NEC correction-table range. Insulation and terminal ratings display both units while retaining the code-table Celsius values as the calculation basis.
- Select the base ampacity from the conductor material, size, and insulation-temperature column.
- Multiply by the Table 310.15(B)(1)(1) ambient-temperature correction factor.
- Multiply by the Table 310.15(C)(1) factor for the entered number of current-carrying conductors.
- Compare that result with the unadjusted Table 310.16 ampacity at the selected equipment-terminal temperature.
- For the general load check, compare the lower applicable value with noncontinuous load plus 125% of continuous load.
- Where displayed, apply the general NEC 240.4(D) small-conductor overcurrent-protection cap as an additional planning limitation.
The minimum-size comparison repeats that same calculation for every supported Table 310.16 conductor of the selected material, in table order. The first size whose planning limit meets or exceeds the load requirement is labeled as the minimum passing size. Nearby rows are shown for comparison. This is not a parallel-conductor design or an evaluation of exceptions, voltage drop, equipment configuration, or product availability.
The calculator does not decide whether a neutral counts, whether an exception to adjustment applies, or whether special motor, HVAC, dwelling-service, rooftop, tray, parallel-conductor, or equipment rules govern. Terminal rating must come from the applicable equipment marking and the lowest applicable termination in the circuit must be considered.
Primary references: NFPA 70, 2023 edition, the Southwire THHN/THWN-2 engineering table citing 2023 NEC Table 310.16, and UL Solutions panelboard terminal-temperature guidance.
Equipment grounding conductor method
The Equipment Grounding Conductor Calculator is intentionally limited to one wire-type EGC in one non-parallel raceway through 600 A. It reproduces the supported portion of 2023 NEC Table 250.122 using the entered automatic overcurrent-device rating or setting.
- Select the base copper or aluminum EGC size from Table 250.122.
- Divide the installed phase-conductor circular-mil area by the minimum phase-conductor area that has sufficient ampacity for the intended installation.
- Multiply the base EGC circular-mil area by that phase-conductor area ratio.
- Select the next supported standard EGC size meeting or exceeding the calculated area, without requiring an EGC larger than the installed circuit conductor.
The conduit handoff creates separate phase-conductor and EGC rows, but it does not select a manufacturer. The user must choose the exact insulation and listed product so conduit fill uses verified outside diameters. Primary reference: NFPA 70, 2023 edition.
Conduit Fill and Conduit Size also offer an electrical-only option to calculate and include one wire-type EGC directly. The same method is used, and the result is added as one physical conductor in the raceway only after an exact published insulated product diameter is selected. It counts toward conduit fill but is not presented as a current-carrying conductor for ampacity adjustment. The option is not shown for telecommunications, data, AV, security, fiber, or other low-voltage cable projects.
The calculator does not determine the overcurrent device, phase ampacity, raceway suitability as an EGC, effective fault-current path, parallel-raceway rules, motors, taps, material installation restrictions, special equipment requirements, or final compliance.
Electrical box-fill method
The Electrical Box Fill Calculator implements the six allowance categories in 2023 NEC 314.16(B) for 18 AWG through 6 AWG conductors in one undivided outlet, device, or junction-box space. The user must supply and explicitly confirm the usable assembled volume established under 314.16(A). The calculation passes when that available volume is greater than or equal to the sum of the applicable allowances.
Table 314.16(B) volume allowances used by the calculation are 1.50 in³ for 18 AWG, 1.75 in³ for 16 AWG, 2.00 in³ for 14 AWG, 2.25 in³ for 12 AWG, 2.50 in³ for 10 AWG, 3.00 in³ for 8 AWG, and 5.00 in³ for 6 AWG. The published metric allowances are 24.6, 28.7, 32.8, 36.9, 41.0, 49.2, and 81.9 cm³, respectively. The selected table column is used directly, and values remain unrounded in the pass/fail comparison.
- Each entering conductor that terminates or is spliced and each unspliced pass-through receives one allowance at its conductor size. A loop or coil of unbroken conductor receives two only when it is at least twice the minimum free-conductor length required by 300.14; conductors entirely contained in the box receive none.
- One or more ordinary internal cable clamps share one allowance based on the largest conductor present. A cable connector whose clamp mechanism is outside the box receives no clamp allowance.
- Luminaire studs and hickeys each receive one allowance per fitting type, based on the largest conductor present.
- Each device yoke or strap receives two allowances based on the largest conductor connected to it. Equipment wider than one 2-inch device box is entered using the number of gangs required for mounting.
- Up to four equipment grounding conductors that enter the box share one allowance based on the largest entering equipment grounding conductor. Each additional entering equipment grounding conductor adds one-quarter allowance. An equipment bonding jumper that begins and ends within the box is not included.
- Each terminal-block assembly receives one allowance based on the largest conductor terminated to that assembly. This sixth category was added in the 2023 edition.
Small fittings such as locknuts and bushings do not receive separate allowances. The calculator also does not add wire connectors or internal pigtails whose entire length remains in the box. An integral clamp assembly that incorporates cable terminations has special listing, conductor-count, and marked-volume treatment and is outside the ordinary-clamp control presented here.
The clamp and support-fitting input requires the largest conductor physically present in the box. That governing size includes a conductor that stays entirely inside the box even though that conductor receives no separate allowance under 314.16(B)(1). The calculator rejects a selected fitting size smaller than any conductor size entered elsewhere.
Each space separated by a barrier must be calculated independently; the calculator does not combine volume across barriers. It also does not size conduit bodies under 314.16(C), evaluate conductors 4 AWG or larger and their additional 314.28 requirements, or apply 314.16 to motor or generator terminal housings. The luminaire-canopy exception must be evaluated separately against every condition in the adopted code text. The calculator does not determine box depth, conductor bending space, conductor permissions, box listing, installation support, accessibility, or complete compliance.
Primary references: NFPA 70, 2023 edition, the official NFPA 314.16 development text and allowance table, and the official NFPA 2023 grounding and terminal-block revision record.
Pull-box sizing method
The Pull Box Size Calculator records each physical conduit once, including conduits entering through the back mounting surface, and records the cable or conductor connections between those openings. Its Power and cable-planning modes use separate methods.
Power conductors
- Straight pulls use eight times the largest applicable conduit trade size in the pull direction.
- Angle and U pulls are evaluated conservatively by affected wall using six times the largest conduit trade size plus the trade sizes of other conduit entries on that wall.
- When multiple requirements affect one plan dimension, the largest calculated requirement governs.
- The applicable paired conduit entry-to-exit spacing requirement is reported. Actual spacing is not passed or failed because knockout-center positions are not entered.
- For a Back entry opposite the cover, optional largest-conductor data enables the NEC 314.28(A)(2) and Table 312.6(A) one-wire-per-terminal front-to-cover depth check for 4 AWG through 2000 kcmil power conductors.
Power-mode length, width, and any calculated Back-entry depth are compared with the proposed usable inside dimensions. When optional conductor data is omitted, no conductor size is assumed and depth remains unverified. When only some Back entries include conductor data, the reported depth is provisional because an omitted entry could govern. A dimension not governed by the entered layout remains a physical-fit review.
Communications and fiber cable
These modes do not reuse the NEC power-conductor multipliers. The user may start with a quick-planning review that documents the enclosure and conduit layout without applying a generic bend-radius assumption. Optional manufacturer data adds the actual cable or bundle outside diameter, the manufacturer's installation and installed bend radii, optional additional total routing clearance, and the enclosure plane containing the bend. The larger entered radius governs.
When those optional details are complete, the conservative full-bend envelope is 2R + cable or bundle outside diameter + additional total clearance. Both usable inside dimensions in the selected bend plane are checked against that envelope. Without them, no cable minimum is calculated and all proposed dimensions remain project verification items. Either workflow remains REVIEW because entry positions, pulling tension, hardware, service loops, splice trays, firestopping, manufacturer instructions, TIA/BICSI guidance, and project requirements can require more space.
Verify the actual physical layout and knockout-center spacing separately. See the pull-box instructions or open the Pull Box Size Calculator.
Jam-ratio method
Jam ratio is calculated as conduit inside diameter divided by the outside diameter of one identical round cable. The calculator uses the selected conduit library dimension and the selected manufacturer cable diameter, or a user-entered custom diameter.
Published cable-manufacturer guidance classifies ratios below 2.3 as very small risk, 2.3 through below 2.6 as small, 2.6 through below 2.8 as moderate, 2.8 through below 3.0 as significant, 3.0 through below 3.1 as moderate, 3.1 through below 3.2 as small, and 3.2 or greater as very small. Those published bands account for conduit-bend ovality; the calculator therefore does not apply another hidden diameter reduction.
The published risk classification is shown only for three or more identical round cables. Southwire identifies a triangular three-cable configuration below a 2.5 ratio and a cradled configuration at 2.5 or greater. Mixed cable diameters and complete pulling design require a more detailed analysis.
Cable quantity does not appear in the jam-ratio formula and therefore does not change the published risk range once three or more identical cables are present. Quantity does affect whether the cables fit. The calculator separately applies the automatic conduit-fill percentage for the entered quantity, calculates occupied conduit area, and reports the maximum whole number of identical cables permitted. A fill failure is presented as the governing result before the jam-ratio category.
Sources: Southwire Power Cable Installation Guide and Cerrowire Installation Information.
Cable-tray fill method
The Cable Tray Fill Calculator provides two deliberately separate workflows. Area fill sums π × (outside diameter ÷ 2)² × quantity for every round cable and compares that occupied area with inside tray width × usable depth × the documented fill percentage. Single-layer width sums outside diameter × quantity and compares the result directly with the tray inside width.
An optional user-selected installation allowance increases the geometric cable demand for planning purposes before pass/fail and recommended-width calculations are performed. The default is 0%. The 20% option is identified as a recommendation for typical field conditions, not as a code-mandated packing factor. Reports show the raw geometric demand and adjusted planning demand separately.
The minimum width is calculated by rearranging the selected equation. The recommended width is the smallest available generic or manufacturer width equal to or greater than that minimum. Published tray dimensions for Eaton B-Line, Legrand Cablofil, nVent HOFFMAN, Hubbell, and Snake Tray are stored separately from the calculation rules so product data can be updated or expanded without changing the mathematics.
Eaton's cable-tray design guidance documents the distinction between area-based cable groups and cables required to occupy a single layer. nVent's published wire-mesh guidance documents the same round-cable area formula and a 50% control-cable example. The user must select the method and percentage supported by the actual cable classification and governing requirements.
The result does not verify tray structural load class, support span, cable ampacity, conductor adjustment, grounding, separation, firestopping, or power-cable-specific rules. See the cable-tray instructions.
Multi-conduit capacity plan
When the cable load exceeds the largest available conduit, the calculator determines the minimum number of the largest available size required by combined fill capacity. It then reduces the final conduit to the smallest available size that supplies the remaining capacity.
The displayed plan is a capacity plan, not a final installation design. The calculator distributes larger cable types first, then shares each cable type proportionally across the remaining conduit capacities. Every conduit displays its assigned quantities and calculated fill.
The distribution uses the selected fill limit consistently across the plan. Confirm cable routing, pulling conditions, project specifications, and applicable installation requirements before use.
Users may adopt the recommended plan or build an editable plan with two or more conduits. When conduit types or sizes are changed, the calculator redistributes the complete cable load automatically and validates every conduit run separately. A selected plan passes only when every cable is allocated and every conduit remains within the permitted fill.
Fill methods
- Recommended low-voltage fill: 40%. This is the calculator default.
- Automatic electrical fill: 53% for one cable or conductor, 31% for two, and 40% for three or more.
- Conservative fill: 30%.
- Manual fill: a user-entered value greater than 0% and no more than 100%.
The low-voltage, conservative, and manual modes are planning choices; they do not replace project specifications or applicable code requirements.
Smallest-conduit recommendation
The minimum required conduit internal area is calculated as combined cable area ÷ permitted fill decimal. The calculator then compares that value with the available conduits in the selected family and recommends the smallest conduit whose internal area is equal to or greater than the requirement.
Cable calculations retain full JavaScript numeric precision. Published conduit internal areas use the documented three-decimal dataset values; no additional rounding is applied when choosing the recommendation.
A recommendation does not automatically change the selected conduit. Users may review it and choose whether to apply it.
EMT dimensional reference
EMT inside diameters from 1/2 through 4 inches use manufacturer nominal values published in the Wheatland Tube EMT & Conduit brochure, accessed July 23, 2026.
Internal area is calculated from the published nominal inside diameter using π × (inside diameter ÷ 2)² and rounded to three decimal places. Wheatland identifies its inside diameter values as informational rather than requirements of UL 797.
Bend information and optional planning allowances
NEC Chapter 9 raceway-fill percentages do not change based on the number of bends. The calculator therefore uses no bend-based fill reduction by default. Entered bend angles are still reported and evaluated for pathway warnings independently from the fill method.
When a cable manufacturer, project specification, or authority having jurisdiction requires an additional planning allowance, the user may select a 15% relative capacity reduction per 90-degree equivalent. The equivalent bend count is total entered degrees divided by 90. The capacity factor is 1 minus the equivalent bend count multiplied by 0.15, and the effective fill percentage is the base fill percentage multiplied by that factor. For example, two 90-degree bends produce a 0.70 factor, changing a 40% base criterion to a 28% project-planning limit.
A third option accepts a project-approved method that applies no reduction to the first two 90-degree equivalents, then reduces capacity by 15% for each additional 90-degree equivalent. Fractional equivalents are applied proportionally. For example, 225 degrees equals 2.5 bend equivalents, so 0.5 equivalent is chargeable and a 40% base fill becomes 37%.
A fourth option accepts a project-approved custom adjusted fill percentage. This permits the calculator to follow a documented manufacturer or project requirement without presenting that value as a universal code or industry-standard rule.
The optional reductions are planning methods, not NEC Chapter 9 requirements. None of the three modes calculates pulling tension, sidewall pressure, bend-radius compliance, cable jamming, lubricant performance, or manufacturer pulling limits. Bend warnings remain active regardless of the selected fill treatment.
RMC and IMC dimensional references
Steel rigid metal conduit sizes 1/2 through 6 inches use manufacturer nominal inside diameters from the Wheatland Tube DuraGuard RMC brochure. Steel intermediate metal conduit sizes 1/2 through 4 inches use manufacturer nominal inside diameters from the Wheatland Tube IMC brochure. Both sources were accessed and verified July 23, 2026.
Internal area is calculated from each published nominal inside diameter using π × (inside diameter ÷ 2)² and rounded to three decimal places.
PVC conduit dimensional references
Solid-wall PVC Schedule 40 and Schedule 80 electrical conduit sizes 1/2 through 6 inches use manufacturer nominal inside diameters published in the JM Eagle Solvent Weld PVC Electrical Conduit Schedule Series data sheet, accessed and verified July 24, 2026.
Internal area is calculated from each published nominal inside diameter using π × (inside diameter ÷ 2)² and rounded to three decimal places. Cellular-core conduit values are not used.
Cable-library references
Preset cable diameters use nominal overall diameters from the linked manufacturer specifications. The electrical-power library includes stranded Southwire, Encore Wire, and Cerrowire building-wire products: copper THHN/THWN-2, copper XHHW-2/RW90, and the published Southwire aluminum XHHW-2/RW90 family. The 128 nominal dimensions include separately identified stranded products plus published 14, 12, and 10 AWG solid copper THHN/THWN-2 products from Encore Wire and Cerrowire. They were verified August 1, 2026; other cable entries retain their individually recorded verification dates. Confirm the exact product construction, voltage rating, revision, and measured diameter selected for a project.
Electrical conductor presets provide insulated outside diameter for pathway-area calculations. They do not independently establish ampacity, terminal temperature compatibility, current-carrying conductor adjustment, ambient correction, grounding-conductor size, or code compliance.
Electrical product labels follow the same order in every applicable calculator. Electrical-only filters narrow conductor material, insulation designation, and solid or stranded construction before manufacturer and conductor size. Manufacturer remains a separate selection because nominal outside diameter can differ between products with the same conductor size and insulation designation.
- Southwire SIMpull THHN/THWN-2 copper 14 AWG stranded single conductor: 0.102 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 12 AWG stranded single conductor: 0.119 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 10 AWG stranded single conductor: 0.150 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 8 AWG stranded single conductor: 0.217 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 6 AWG stranded single conductor: 0.253 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 4 AWG stranded single conductor: 0.322 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 3 AWG stranded single conductor: 0.350 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 2 AWG stranded single conductor: 0.384 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 1 AWG stranded single conductor: 0.441 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 1/0 AWG stranded single conductor: 0.480 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 2/0 AWG stranded single conductor: 0.524 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 3/0 AWG stranded single conductor: 0.574 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 4/0 AWG stranded single conductor: 0.627 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 250 kcmil stranded single conductor: 0.684 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 300 kcmil stranded single conductor: 0.753 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 350 kcmil stranded single conductor: 0.803 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 400 kcmil stranded single conductor: 0.848 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 500 kcmil stranded single conductor: 0.931 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 600 kcmil stranded single conductor: 1.030 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 750 kcmil stranded single conductor: 1.132 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull THHN/THWN-2 copper 1000 kcmil stranded single conductor: 1.281 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 14 AWG stranded single conductor: 0.131 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 12 AWG stranded single conductor: 0.147 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 10 AWG stranded single conductor: 0.173 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 8 AWG stranded single conductor: 0.238 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 6 AWG stranded single conductor: 0.274 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 4 AWG stranded single conductor: 0.321 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 3 AWG stranded single conductor: 0.348 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 2 AWG stranded single conductor: 0.379 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 1 AWG stranded single conductor: 0.435 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 1/0 AWG stranded single conductor: 0.480 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 2/0 AWG stranded single conductor: 0.524 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 3/0 AWG stranded single conductor: 0.574 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 4/0 AWG stranded single conductor: 0.630 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 250 kcmil stranded single conductor: 0.700 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 300 kcmil stranded single conductor: 0.753 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 350 kcmil stranded single conductor: 0.803 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 400 kcmil stranded single conductor: 0.848 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 500 kcmil stranded single conductor: 0.908 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 600 kcmil stranded single conductor: 1.038 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 750 kcmil stranded single conductor: 1.140 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 copper 1000 kcmil stranded single conductor: 1.289 in nominal outside diameter; XHHW-2; 600/1000 V for applicable XHHW-2 sizes; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 8 AWG stranded single conductor: 0.230 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 6 AWG stranded single conductor: 0.265 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 4 AWG stranded single conductor: 0.309 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 2 AWG stranded single conductor: 0.364 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 1 AWG stranded single conductor: 0.415 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 1/0 AWG stranded single conductor: 0.452 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 2/0 AWG stranded single conductor: 0.492 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 3/0 AWG stranded single conductor: 0.539 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 4/0 AWG stranded single conductor: 0.591 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 250 kcmil stranded single conductor: 0.658 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 300 kcmil stranded single conductor: 0.708 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 350 kcmil stranded single conductor: 0.754 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 400 kcmil stranded single conductor: 0.797 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 500 kcmil stranded single conductor: 0.876 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 600 kcmil stranded single conductor: 0.981 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 750 kcmil stranded single conductor: 1.076 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Southwire SIMpull XHHW-2/RW90 AlumaFlex aluminum 1000 kcmil stranded single conductor: 1.228 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected product; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 14 AWG stranded single conductor: 0.109 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 12 AWG stranded single conductor: 0.128 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 10 AWG stranded single conductor: 0.161 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 8 AWG stranded single conductor: 0.213 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 6 AWG stranded single conductor: 0.249 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 4 AWG stranded single conductor: 0.318 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 3 AWG stranded single conductor: 0.346 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 2 AWG stranded single conductor: 0.378 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 1 AWG stranded single conductor: 0.435 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 1/0 AWG stranded single conductor: 0.474 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 2/0 AWG stranded single conductor: 0.518 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 3/0 AWG stranded single conductor: 0.568 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 4/0 AWG stranded single conductor: 0.624 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 250 kcmil stranded single conductor: 0.678 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 300 kcmil stranded single conductor: 0.730 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 350 kcmil stranded single conductor: 0.777 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 400 kcmil stranded single conductor: 0.821 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 500 kcmil stranded single conductor: 0.902 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 600 kcmil stranded single conductor: 1.051 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 750 kcmil stranded single conductor: 1.156 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 1000 kcmil stranded single conductor: 1.310 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 14 AWG stranded single conductor: 0.131 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 12 AWG stranded single conductor: 0.150 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 10 AWG stranded single conductor: 0.173 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 8 AWG stranded single conductor: 0.236 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 6 AWG stranded single conductor: 0.274 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 4 AWG stranded single conductor: 0.322 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 3 AWG stranded single conductor: 0.350 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 2 AWG stranded single conductor: 0.382 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 1 AWG stranded single conductor: 0.431 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 1/0 AWG stranded single conductor: 0.470 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 2/0 AWG stranded single conductor: 0.514 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 3/0 AWG stranded single conductor: 0.564 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 4/0 AWG stranded single conductor: 0.620 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 250 kcmil stranded single conductor: 0.672 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 300 kcmil stranded single conductor: 0.724 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 350 kcmil stranded single conductor: 0.771 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 400 kcmil stranded single conductor: 0.815 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 500 kcmil stranded single conductor: 0.896 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 600 kcmil stranded single conductor: 1.053 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 750 kcmil stranded single conductor: 1.158 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite XHHW-2/RW90 copper 1000 kcmil stranded single conductor: 1.312 in nominal outside diameter; XHHW-2; 600/1000 V; verify selected application; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 14 AWG stranded single conductor: 0.111 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 12 AWG stranded single conductor: 0.130 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 10 AWG stranded single conductor: 0.164 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 8 AWG stranded single conductor: 0.216 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 6 AWG stranded single conductor: 0.254 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 4 AWG stranded single conductor: 0.324 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 3 AWG stranded single conductor: 0.352 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 2 AWG stranded single conductor: 0.384 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 1 AWG stranded single conductor: 0.446 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 1/0 AWG stranded single conductor: 0.486 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 2/0 AWG stranded single conductor: 0.532 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 3/0 AWG stranded single conductor: 0.584 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 4/0 AWG stranded single conductor: 0.642 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 250 kcmil stranded single conductor: 0.711 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 300 kcmil stranded single conductor: 0.766 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 350 kcmil stranded single conductor: 0.817 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 400 kcmil stranded single conductor: 0.864 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 500 kcmil stranded single conductor: 0.949 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 600 kcmil stranded single conductor: 1.051 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 750 kcmil stranded single conductor: 1.156 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire SLiPWire THHN/THWN-2 copper 1000 kcmil stranded single conductor: 1.310 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 14 AWG solid single conductor: 0.101 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 12 AWG solid single conductor: 0.120 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Encore Wire SuperSlick Elite THHN/THWN-2 copper 10 AWG solid single conductor: 0.149 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire THHN/THWN-2 copper 14 AWG solid single conductor: 0.104 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire THHN/THWN-2 copper 12 AWG solid single conductor: 0.120 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Cerrowire THHN/THWN-2 copper 10 AWG solid single conductor: 0.151 in nominal outside diameter; THHN/THWN-2; 600 V; 90°C maximum per published application conditions
- Belden 1212 Category 5e U/UTP CMR: 0.206 in nominal outside diameter; CMR
- Belden 2412 Category 6 U/UTP CMR: 0.224 in nominal outside diameter; CMR
- Belden 10GXM13 Category 6A U/UTP CMP: 0.230 in nominal outside diameter; CMP
- Belden 10GXW13 Category 6A U/UTP CMP: 0.250 in nominal outside diameter; CMP
- Belden 2413 Category 6+ Enhanced U/UTP plenum cable CMP: 0.224 in nominal outside diameter; CMP
- Belden 3612 Category 6+ Premium U/UTP riser cable CMR: 0.231 in nominal outside diameter; CMR
- Belden 3613 Category 6+ Premium U/UTP plenum cable CMP: 0.238 in nominal outside diameter; CMP
- Belden 2413F Category 6+ Enhanced shielded F/UTP plenum cable CMP: 0.285 in nominal outside diameter; CMP
- Belden 7928A DataTuff industrial Category 5e bonded-pair plenum cable CMP: 0.183 in nominal outside diameter; CMP
- Belden 7934A DataTuff industrial Category 5e outdoor direct-burial cable: 0.230 in nominal outside diameter; Outdoor / direct burial
- Belden D5FR Category 5e shielded F/UTP riser cable CMR: 0.260 in nominal outside diameter; CMR
- Belden 7922A DataTuff industrial Category 5e 22 AWG PLTC/CMR cable: 0.301 in nominal outside diameter; PLTC / CMR / CMX Outdoor
- Belden 11700A DataTuff industrial Category 5e double-jacket riser cable CMR: 0.285 in nominal outside diameter; CMR
- CommScope 2071E GigaSPEED XL Category 6 U/UTP CMP: 0.226 in nominal outside diameter; CMP
- CommScope 2091B GigaSPEED X10D Category 6A U/UTP CMP: 0.285 in nominal outside diameter; CMP
- Superior Essex 10Gain XP Category 6A U/UTP riser cable CMR: 0.275 in nominal outside diameter; CMR
- Superior Essex 10Gain XP Category 6A U/UTP plenum cable CMP: 0.265 in nominal outside diameter; CMP
- Superior Essex 10Gain Category 6A U/UTP riser cable CMR: 0.350 in nominal outside diameter; CMR
- Superior Essex 10Gain Category 6A U/UTP plenum cable CMP: 0.320 in nominal outside diameter; CMP
- Superior Essex Category 6A U/FTP shielded riser cable CMR: 0.320 in nominal outside diameter; CMR
- Superior Essex Category 6A U/FTP shielded plenum cable CMP: 0.320 in nominal outside diameter; CMP
- Superior Essex Category 5e F/UTP shielded riser cable CMR: 0.260 in nominal outside diameter; CMR
- Superior Essex Category 5e F/UTP shielded plenum cable CMP: 0.250 in nominal outside diameter; CMP
- Superior Essex 77 Series Category 6 U/UTP CMR/CMX outdoor cable: 0.270 in nominal outside diameter; CMR/CMX Outdoor
- Superior Essex PowerWise 1G Category 5e cable for 4-pair PoE, CMR: 0.230 in nominal outside diameter; CMR
- Superior Essex PowerWise 1G Category 5e cable for 4-pair PoE, CMP: 0.230 in nominal outside diameter; CMP
- Superior Essex Marathon LAN Category 5e U/UTP riser cable: 0.180 in nominal outside diameter; CMR
- Superior Essex Marathon LAN Category 5e U/UTP plenum cable: 0.190 in nominal outside diameter; CMP
- Superior Essex premises indoor/outdoor dry tight-buffer fiber cable, 6 fiber: 0.230 in nominal outside diameter; OFNP
- Superior Essex premises indoor/outdoor dry tight-buffer fiber cable, 12 fiber: 0.300 in nominal outside diameter; OFNP
- Superior Essex premises indoor/outdoor dry tight-buffer fiber cable, 24 fiber: 0.320 in nominal outside diameter; OFNP
- Superior Essex premises indoor/outdoor dry multi-unit tight-buffer fiber cable, 48 fiber: 0.670 in nominal outside diameter; OFNP
- Superior Essex 2x2 hybrid cable with two fibers and two copper conductors, unarmored: 0.330 in nominal outside diameter; Indoor/Outdoor Riser
- Superior Essex 2x2 hybrid cable with two fibers and two copper conductors, armored: 0.640 in nominal outside diameter; Armored Direct Burial
- Superior Essex 18 AWG 2-conductor shielded fire alarm cable: 0.160 in nominal outside diameter; FPLR/CL3R/CMR
- Superior Essex 18 AWG 2-conductor shielded fire alarm cable: 0.160 in nominal outside diameter; FPLP/CL3P/CMP
- Superior Essex 16 AWG 2-conductor shielded fire alarm cable: 0.180 in nominal outside diameter; FPLR/CL3R/CMR
- Superior Essex 16 AWG 2-conductor shielded fire alarm cable: 0.180 in nominal outside diameter; FPLP/CL3P/CMP
- Berk-Tek LANMARK-1000 enhanced Category 6 U/UTP riser cable CMR: 0.230 in nominal outside diameter; CMR
- Berk-Tek LANMARK-6 compact Category 6 U/UTP riser cable CMR: 0.230 in nominal outside diameter; CMR
- Berk-Tek LANMARK-6 compact Category 6 U/UTP plenum cable CMP: 0.230 in nominal outside diameter; CMP
- Berk-Tek LANMARK-6 shielded Category 6 F/UTP plenum cable CMP: 0.275 in nominal outside diameter; CMP
- Berk-Tek SST high-performance Category 6A U/UTP riser cable CMR: 0.275 in nominal outside diameter; CMR
- Berk-Tek SST high-performance Category 6A U/UTP plenum cable CMP: 0.255 in nominal outside diameter; CMP
- Berk-Tek SST high-performance Category 6A U/UTP outdoor cable CMX: 0.275 in nominal outside diameter; CMX
- Berk-Tek ICR-I/O tight-buffered single-fiber indoor/outdoor riser interconnect cable: 0.114 in nominal outside diameter; OFNR
- Berk-Tek ICR-I/O tight-buffered 2-fiber indoor/outdoor riser interconnect cable: 0.187 in nominal outside diameter; OFNR
- Berk-Tek ICR-I/O tight-buffered 4-fiber indoor/outdoor riser interconnect cable: 0.187 in nominal outside diameter; OFNR
- Berk-Tek PDP-I/O tight-buffered 6-fiber indoor/outdoor plenum distribution cable: 0.180 in nominal outside diameter; OFNP
- Berk-Tek PDP-I/O tight-buffered 12-fiber indoor/outdoor plenum distribution cable: 0.215 in nominal outside diameter; OFNP
- Berk-Tek PDP-I/O tight-buffered 24-fiber indoor/outdoor plenum distribution cable: 0.288 in nominal outside diameter; OFNP
- Berk-Tek PDP-I/O subunitized 36-fiber indoor/outdoor plenum distribution cable: 0.521 in nominal outside diameter; OFNP
- Berk-Tek PDP-I/O subunitized 48-fiber indoor/outdoor plenum distribution cable: 0.558 in nominal outside diameter; OFNP
- Berk-Tek PDP-I/O subunitized 72-fiber indoor/outdoor plenum distribution cable: 0.716 in nominal outside diameter; OFNP
- Berk-Tek PDP-I/O subunitized 96-fiber indoor/outdoor plenum distribution cable: 0.859 in nominal outside diameter; OFNP
- Berk-Tek PDP-I/O subunitized 144-fiber indoor/outdoor plenum distribution cable: 0.896 in nominal outside diameter; OFNP
- Berk-Tek PDPK-I/O ARMOR-TEK 6-fiber indoor/outdoor armored plenum cable: 0.499 in nominal outside diameter; OFCP/OFNP
- Berk-Tek PDPK-I/O ARMOR-TEK 12-fiber indoor/outdoor armored plenum cable: 0.527 in nominal outside diameter; OFCP/OFNP
- Berk-Tek PDPK-I/O ARMOR-TEK 24-fiber indoor/outdoor armored plenum cable: 0.590 in nominal outside diameter; OFCP/OFNP
- Berk-Tek PDPK-I/O ARMOR-TEK 36-fiber indoor/outdoor armored plenum cable: 0.821 in nominal outside diameter; OFCP/OFNP
- Berk-Tek PDPK-I/O ARMOR-TEK 48-fiber indoor/outdoor armored plenum cable: 0.921 in nominal outside diameter; OFCP/OFNP
- Berk-Tek PDPK-I/O ARMOR-TEK 72-fiber indoor/outdoor armored plenum cable: 0.974 in nominal outside diameter; OFCP/OFNP
- Berk-Tek PDPK-I/O ARMOR-TEK 96-fiber indoor/outdoor armored plenum cable: 1.225 in nominal outside diameter; OFCP/OFNP
- Berk-Tek PDPK-I/O ARMOR-TEK 144-fiber indoor/outdoor armored plenum cable: 1.225 in nominal outside diameter; OFCP/OFNP
- Berk-Tek RDT reduced-diameter Category 6A U/UTP riser cable CMR: 0.245 in nominal outside diameter; CMR
- Berk-Tek RDT reduced-diameter Category 6A U/UTP plenum cable CMP: 0.230 in nominal outside diameter; CMP
- Panduit TX6 Category 6 U/UTP riser cable CMR: 0.203 in nominal outside diameter; CMR
- Panduit TX6 Category 6 U/UTP plenum cable CMP: 0.203 in nominal outside diameter; CMP
- Panduit TX6A 10Gig Category 6A U/UTP plenum cable CMP: 0.250 in nominal outside diameter; CMP
- Panduit TX6A-SD small-diameter Category 6A U/UTP riser cable CMR: 0.240 in nominal outside diameter; CMR
- Panduit TX6A-SD small-diameter Category 6A U/UTP plenum cable CMP: 0.240 in nominal outside diameter; CMP
- Panduit Opti-Core OM3 6-fiber all-dielectric central-tube indoor/outdoor cable: 0.310 in nominal outside diameter; LSZH
- Panduit Opti-Core OM3 12-fiber all-dielectric central-tube indoor/outdoor cable: 0.310 in nominal outside diameter; LSZH
- Panduit Opti-Core OM3 24-fiber all-dielectric stranded-tube indoor/outdoor cable: 0.430 in nominal outside diameter; LSZH
- Panduit Opti-Core OM3 48-fiber all-dielectric stranded-tube indoor/outdoor cable: 0.430 in nominal outside diameter; LSZH
- Panduit Opti-Core OM4 6-fiber all-dielectric central-tube indoor/outdoor cable: 0.310 in nominal outside diameter; LSZH
- Panduit Opti-Core OM4 12-fiber all-dielectric central-tube indoor/outdoor cable: 0.310 in nominal outside diameter; LSZH
- Panduit Opti-Core OM4 24-fiber all-dielectric stranded-tube indoor/outdoor cable: 0.430 in nominal outside diameter; LSZH
- Panduit Opti-Core OM4 48-fiber all-dielectric stranded-tube indoor/outdoor cable: 0.430 in nominal outside diameter; LSZH
- Panduit Opti-Core OS2 6-fiber all-dielectric central-tube indoor/outdoor cable: 0.310 in nominal outside diameter; LSZH
- Panduit Opti-Core OS2 12-fiber all-dielectric central-tube indoor/outdoor cable: 0.310 in nominal outside diameter; LSZH
- Panduit Opti-Core OS2 24-fiber all-dielectric stranded-tube indoor/outdoor cable: 0.430 in nominal outside diameter; LSZH
- Panduit Opti-Core OS2 48-fiber all-dielectric stranded-tube indoor/outdoor cable: 0.430 in nominal outside diameter; LSZH
- Panduit Opti-Core OS2 12-fiber indoor ribbon cable: 0.380 in nominal outside diameter; OFNP
- Panduit Opti-Core OS2 48-fiber indoor ribbon cable: 0.380 in nominal outside diameter; OFNP
- Panduit Opti-Core OS2 96-fiber indoor ribbon cable: 0.400 in nominal outside diameter; OFNP
- Panduit Opti-Core OM4 12-fiber indoor ribbon cable: 0.380 in nominal outside diameter; OFNP
- Panduit Opti-Core OM4 48-fiber indoor ribbon cable: 0.380 in nominal outside diameter; OFNP
- Panduit Opti-Core OM4 96-fiber indoor ribbon cable: 0.400 in nominal outside diameter; OFNP
- CommScope 1071E GigaSPEED XL Category 6 U/UTP riser cable CMR: 0.232 in nominal outside diameter; CMR
- CommScope 1091B GigaSPEED X10D Category 6A U/UTP riser cable CMR: 0.285 in nominal outside diameter; CMR
- CommScope 1061B PowerSUM Category 5e U/UTP riser cable CMR: 0.205 in nominal outside diameter; CMR
- CommScope 2061F PowerSUM Category 5e U/UTP plenum cable CMP: 0.200 in nominal outside diameter; CMP / FT6
- CommScope CS34P Uniprise Category 6 F/UTP plenum cable CMP: 0.273 in nominal outside diameter; CMP / FT6
- CommScope 1572A Category 6 F/UTP outdoor and buried cable: 0.330 in nominal outside diameter; Outdoor / buried
- CommScope 2291B GigaSPEED X10D Category 6A F/UTP plenum cable CMP: 0.276 in nominal outside diameter; CMP
- CommScope 5291A GigaSPEED X10D Category 6A F/UTP low-smoke zero-halogen riser cable: 0.296 in nominal outside diameter; CMR / LSZH
- CommScope 1592A Category 6A F/UTP outdoor and buried cable: 0.330 in nominal outside diameter; Outdoor / buried
- CommScope 3296A Category 6A F/FTP low-smoke zero-halogen cable: 0.276 in nominal outside diameter; LSZH
- CommScope P-006-OD 6-fiber indoor/outdoor fiber-optic cable: 0.213 in nominal outside diameter; Indoor / outdoor
- CommScope P-012-OD 12-fiber indoor/outdoor fiber-optic cable: 0.272 in nominal outside diameter; Indoor / outdoor
- CommScope C-024-CN 24-fiber OS2 loose-tube indoor/outdoor cable: 0.295 in nominal outside diameter; LSZH / CPR Eca
- CommScope C-048-LN 48-fiber OS2 stranded microsheath indoor/outdoor cable: 0.240 in nominal outside diameter; ULSZH / CPR Dca
- CommScope Z-048-LA 48-fiber TeraSPEED armored indoor/outdoor cable: 0.512 in nominal outside diameter; LSZH / CPR Cca
- CommScope 2276V RG6 90-percent-braid plenum coaxial cable: 0.237 in nominal outside diameter; Plenum
- CommScope 2227V RG6 quad-shield plenum coaxial cable: 0.260 in nominal outside diameter; Plenum
- CommScope 2287V RG11 quad-shield plenum coaxial cable: 0.356 in nominal outside diameter; Plenum
- Belden 10GXW12 Category 6A U/UTP riser cable CMR: 0.260 in nominal outside diameter; CMR
- Leviton Atlas-X1 Category 6 U/UTP riser cable CMR: 0.228 in nominal outside diameter; CMR
- Leviton Category 6 U/UTP plenum cable CMP: 0.230 in nominal outside diameter; CMP
- Leviton Atlas-X1 Category 6A U/UTP riser cable CMR: 0.287 in nominal outside diameter; CMR
- Leviton Atlas-X1 Category 6A U/UTP plenum cable CMP: 0.275 in nominal outside diameter; CMP
- Leviton FDT reduced-diameter Category 6A F/UTP plenum cable CMP: 0.235 in nominal outside diameter; CMP
- Leviton SST Category 6A U/UTP plenum cable CMP: 0.250 in nominal outside diameter; CMP
- Leviton OM3 50-micron tight-buffered 6-fiber indoor/outdoor plenum distribution cable: 0.170 in nominal outside diameter; OFNP
- Leviton OM3 50-micron tight-buffered 12-fiber indoor/outdoor plenum distribution cable: 0.205 in nominal outside diameter; OFNP
- Leviton OM3 50-micron tight-buffered 24-fiber indoor/outdoor plenum distribution cable: 0.275 in nominal outside diameter; OFNP
- Leviton OM4 50-micron tight-buffered 6-fiber indoor/outdoor plenum distribution cable: 0.170 in nominal outside diameter; OFNP
- Leviton OM4 50-micron tight-buffered 12-fiber indoor/outdoor plenum distribution cable: 0.205 in nominal outside diameter; OFNP
- Leviton OM4 50-micron tight-buffered 24-fiber indoor/outdoor plenum distribution cable: 0.275 in nominal outside diameter; OFNP
- Leviton OS2 single-mode tight-buffered 6-fiber indoor/outdoor plenum distribution cable: 0.170 in nominal outside diameter; OFNP
- Leviton OS2 single-mode tight-buffered 12-fiber indoor/outdoor plenum distribution cable: 0.205 in nominal outside diameter; OFNP
- Leviton OS2 single-mode tight-buffered 24-fiber indoor/outdoor plenum distribution cable: 0.275 in nominal outside diameter; OFNP
- General Cable GenSPEED 6 Category 6 U/UTP riser cable CMR: 0.220 in nominal outside diameter; CMR
- General Cable GenSPEED 6 Category 6 U/UTP plenum cable CMP: 0.205 in nominal outside diameter; CMP
- General Cable GenSPEED 5000 Category 5e U/UTP riser cable CMR: 0.195 in nominal outside diameter; CMR
- General Cable GenSPEED 5000 Category 5e U/UTP plenum cable CMP: 0.180 in nominal outside diameter; CMP
- General Cable GenSPEED 5000 Category 5e 25-pair backbone riser cable CMR: 0.500 in nominal outside diameter; CMR
- General Cable GenSPEED 5000 Category 5e 25-pair backbone plenum cable CMP: 0.500 in nominal outside diameter; CMP
- General Cable GenSPEED 10 Category 6A shielded F/UTP riser cable CMR: 0.265 in nominal outside diameter; CMR
- General Cable GenSPEED 10 Category 6A shielded F/UTP plenum cable CMP: 0.260 in nominal outside diameter; CMP
- General Cable CAROL four-element composite access-control plenum cable with all elements shielded: 0.430 in nominal outside diameter; CMP
- General Cable CAROL four-element composite access-control plenum cable with one shielded element: 0.420 in nominal outside diameter; CMP
- General Cable CAROL four-element composite access-control riser cable with all elements shielded: 0.430 in nominal outside diameter; CMR
- General Cable CAROL four-element composite access-control riser cable with one shielded element: 0.420 in nominal outside diameter; CMR
- Belden 5320UJ 18/2 solid unshielded fire alarm cable FPL: 0.206 in nominal outside diameter; FPL
- Belden 5000FL 12/2 stranded shielded fire alarm riser cable FPLR: 0.264 in nominal outside diameter; FPLR
- Belden 6000FL 12/2 stranded shielded fire alarm plenum cable FPLP: 0.260 in nominal outside diameter; FPLP
- Belden 5000U2 12/2 waterblocked direct-burial fire alarm cable: 0.340 in nominal outside diameter; CL3 / FPL / PLTC
- West Penn Wire 980 18/2 solid unshielded fire alarm cable FPLR: 0.146 in nominal outside diameter; FPLR
- Belden 5502UH 22/4 stranded security and sound cable CMR: 0.141 in nominal outside diameter; CMR
- Belden 558AMJ 16-conductor access-control composite cable CMP: 0.469 in nominal outside diameter; CMP
- Belden 538HMD1 14-conductor indoor/outdoor OSDP access-control composite cable CM: 0.595 in nominal outside diameter; CM
- Belden 6408MD OSDP data and power access-control composite plenum cable CMP: 0.290 in nominal outside diameter; CMP
- Belden 668AMD 16-conductor dual-OSDP access-control composite plenum cable CMP: 0.480 in nominal outside diameter; CMP
- Belden 551945 surveillance CCTV RG-59 cable CM: 0.232 in nominal outside diameter; CM
- Belden 4694F RG-6/U 75-ohm 12 GHz video coax CM: 0.276 in nominal outside diameter; CM
- Belden 1694A 75-ohm low-loss digital video coax CMR: 0.274 in nominal outside diameter; CMR
- Belden 1505A 75-ohm RG-59 SDI digital video coax riser cable CMR: 0.233 in nominal outside diameter; CMR
- Belden 1506A 75-ohm RG-59 SDI digital video coax plenum cable CMP: 0.196 in nominal outside diameter; CMP
- Belden 1855A 75-ohm mini RG-59 SDI digital video coax: 0.159 in nominal outside diameter; CMR
- Genesis Cable 6360 Category 6 U/UTP riser cable CMR: 0.205 in nominal outside diameter; CMR
- Genesis Cable 5078 Category 5e U/UTP riser cable, 24 AWG, 4 pair: 0.200 in nominal outside diameter; CMR
- Genesis Cable 5088 Category 5e U/UTP plenum cable, 24 AWG, 4 pair: 0.200 in nominal outside diameter; CMP
- Genesis Cable 5178 shielded Category 5e F/UTP riser cable, 24 AWG, 4 pair: 0.250 in nominal outside diameter; CMR
- Genesis Cable 5388 shielded Category 5e F/UTP plenum cable, 24 AWG, 4 pair: 0.230 in nominal outside diameter; CMP
- Genesis Cable 6361 Category 6 U/UTP plenum cable, 23 AWG, 4 pair: 0.205 in nominal outside diameter; CMP
- Genesis Cable 5102 Category 6+ U/UTP plenum cable, 23 AWG, 4 pair: 0.240 in nominal outside diameter; CMP
- Genesis Cable 5192 shielded Category 6+ F/UTP riser cable, 23 AWG, 4 pair: 0.275 in nominal outside diameter; CMR
- Genesis Cable 5392 shielded Category 6+ F/UTP plenum cable, 23 AWG, 4 pair: 0.320 in nominal outside diameter; CMP
- Genesis Cable 5193 Category 6A U/UTP riser cable CMR: 0.276 in nominal outside diameter; CMR
- Genesis Cable 5393 Category 6A U/UTP plenum cable, 23 AWG, 4 pair: 0.252 in nominal outside diameter; CMP
- Genesis Cable 4306 18 AWG, 2-conductor unshielded fire alarm riser cable: 0.134 in nominal outside diameter; FPLR
- Genesis Cable 4311 16 AWG, 2-conductor unshielded fire alarm riser cable: 0.167 in nominal outside diameter; FPLR
- Genesis Cable 4402 18 AWG, 2-conductor shielded fire alarm riser cable: 0.141 in nominal outside diameter; FPLR
- Genesis Cable 4406 16 AWG, 2-conductor shielded fire alarm riser cable: 0.174 in nominal outside diameter; FPLR
- Genesis Cable 4602 18 AWG, 2-conductor shielded fire alarm plenum cable: 0.141 in nominal outside diameter; FPLP
- Genesis Cable 4606 16 AWG, 2-conductor shielded fire alarm plenum cable: 0.172 in nominal outside diameter; FPLP
- Genesis Cable 4156 18 AWG, 2-conductor unshielded direct-burial fire alarm cable: 0.262 in nominal outside diameter; Direct burial / FPL
- Genesis Cable 5502 16 AWG, 2-conductor unshielded NYC-certified fire alarm cable: 0.217 in nominal outside diameter; FPLR / NYC
- Genesis Cable 3196 standard access-control composite cable with an overall plenum jacket: 0.371 in nominal outside diameter; CMP / CL3P
- Genesis Cable 3195 Profusion jacketless access-control composite plenum cable: 0.345 in nominal outside diameter; CMP / CL3P
- Genesis Cable 3296 noisy-environment access-control composite cable with an overall plenum jacket: 0.411 in nominal outside diameter; CMP / CL3P
- Genesis Cable 3295 noisy-environment Profusion jacketless access-control composite plenum cable: 0.385 in nominal outside diameter; CMP / CL3P
- Genesis Cable 5303 RG6/U 18 AWG dual-shield CATV coaxial riser cable: 0.272 in nominal outside diameter; CATVR / CMR / CL2R
- Genesis Cable 5307 RG6/U 18 AWG quad-shield CATV coaxial riser cable: 0.293 in nominal outside diameter; CATVR / CMR / CL2R
- Genesis Cable 5018 RG11/U 14 AWG dual-shield CATV coaxial cable: 0.400 in nominal outside diameter; CATV / CM / CL2
- Remee NY518UH 18/2 unshielded fire alarm cable FPLP: 0.196 in nominal outside diameter; FPLP
- Belden FD4D006P9 indoor/outdoor OM4 distribution tight-buffer fiber cable, 6 fibers: 0.190 in nominal outside diameter; OFNP
- Belden FD4D012P9 indoor/outdoor OM4 distribution tight-buffer fiber cable, 12 fibers: 0.236 in nominal outside diameter; OFNP
- Belden FISD024P9 indoor OS2 distribution tight-buffer fiber cable, 24 fibers: 0.330 in nominal outside diameter; OFNP
- Belden GRAHF48 indoor/outdoor OS2 multi-loose-tube fiber cable, 48 fibers: 0.476 in nominal outside diameter; LSZH / CPR Dca
- Belden FDSD096FK indoor/outdoor OS2 distribution tight-buffer fiber cable, 96 fibers, aluminum interlocked armor: 1.390 in nominal outside diameter; OFCR
- Corning FREEDM One indoor/outdoor tight-buffered OS2 riser cable, 6 fibers: 0.217 in nominal outside diameter; OFNR
- Corning FREEDM One indoor/outdoor tight-buffered OS2 riser cable, 12 fibers: 0.256 in nominal outside diameter; OFNR
- Corning FREEDM One indoor/outdoor tight-buffered OS2 riser cable, 24 fibers: 0.315 in nominal outside diameter; OFNR
- Corning FREEDM One unitized indoor/outdoor tight-buffered OS2 plenum cable, 48 fibers: 0.772 in nominal outside diameter; OFNP
- Corning FREEDM One unitized indoor/outdoor tight-buffered OS2 plenum cable, 96 fibers: 0.728 in nominal outside diameter; OFNP
- Corning indoor drop cable, 1 fiber: 0.094 in nominal outside diameter; Manufacturer family specification
- Corning indoor/outdoor round drop cable, 1 fiber: 0.197 in nominal outside diameter; Manufacturer family specification
- Corning central-tube dielectric armored cable, 2–12 fibers: 0.260 in nominal outside diameter; Manufacturer family specification
Conduit-offset geometry
A standard offset uses the entered vertical rise as its true offset. A rolling offset first combines vertical rise and horizontal roll: true offset = √(rise² + roll²). The rolling rotation angle is atan2(roll, rise).
For two equal bends at angle θ, the offset multiplier is 1 ÷ sin(θ). Ideal centerline travel between bends is true offset × multiplier. Horizontal run is true offset ÷ tan(θ). Theoretical geometric shrink is true offset × tan(θ ÷ 2).
For the standard angles offered by the calculator, the common field-table shrink estimate uses the rounded factor published by Greenlee: 1/16 per unit at 10°, 1/8 at 15°, 3/16 at 22.5°, 1/4 at 30°, 3/8 at 45°, and 1/2 at 60°. This practical estimate is shown separately from exact geometric shrink because the values are not identical.
These equations model idealized centerline geometry. They do not calculate a specific bender's take-up, shoe radius, gain or deduct method, springback, developed bend length, obstruction clearance, or minimum permitted bend radius. Field marks and finished dimensions must be verified using the conduit and bender manufacturer's instructions and the actual installation conditions.
Manufacturer references: Greenlee Site-Rite Hand Bender Use Guide and Klein Tools Conduit Bender Guide.
Saddle and stub-up bending methods
A three-bend saddle uses a center bend and two equal return bends at half the center angle. The published Klein table places each return mark 2.5 times the obstruction height from a 45° center mark, or 2 times the height from a 60° center mark. Published shrink is 3/16 per unit of height at 45° and 1/4 per unit at 60°.
The four-bend saddle is modeled as two equal offsets separated by the entered clear obstruction width. Each offset travel is height ÷ sin(angle). The calculator uses twice the selected common field-table shrink and presents all four marks from the same conduit end. Bend-radius effects and fitting clearance remain field checks.
A 90° stub-up mark is finished stub height minus the exact bender take-up. Custom take-up is the default. Optional Klein hand-bender presets use the published values: 5 inches for 1/2-inch EMT, 6 inches for 3/4-inch EMT or 1/2-inch rigid/IMC, and 8 inches for 1-inch EMT or 3/4-inch rigid/IMC.
Primary references: Klein Tools Conduit Bender Guide, Klein Conduit Bender and Angle Setter Guide, and IDEAL Conduit Bender Guide.
All results are layout aids, not permission to bend a conduit beyond its allowable radius or fill rules. Confirm the actual tool, shoe, conduit type and trade size, springback, obstruction dimensions, available length, and job requirements.
Code and standards context
The documented baseline is NFPA 70, National Electrical Code, 2026 edition. Raceway-fill percentages and applicable raceway dimensions should be checked against the relevant NFPA 70 requirements and tables. Complete NFPA tables are not reproduced here.
A public-source calculation review completed July 23, 2026 confirmed that the 2026 development record directs raceway fill to Chapter 9, Table 1. Published NFPA Chapter 9 committee text documents the 53%, 31%, and 40% limits, use of actual cable dimensions, treatment of a multiconductor or optical-fiber cable as one cable for percentage fill, and the identical-cable 0.8 rounding allowance. Equipment grounding or bonding conductors must also be included when present.
NFPA notes that project conditions such as pull length, bends, alignment, and possible jamming can justify a larger raceway or lower fill. The calculator's optional manufacturer/project and custom-fill methods can model a separately documented planning limit, but neither evaluates the complete physical cable pull.
ANSI/UL 797 is the applicable product standard for steel EMT. It is cited as standards context, not as the source of the nominal inside diameters used by this calculator.
Limitations
Verify the code edition adopted for the project location, project specifications, cable and raceway manufacturer data, pulling conditions, and authority-having-jurisdiction requirements. This calculator does not make installation or compliance decisions.