Voltage Drop Calculator

Voltage Drop Calculator
Calculators

Estimate voltage loss, compare conductor sizes, and coordinate the result with an ampacity minimum. New here? Read the quick guide.

Report details

Circuit inputs and voltage-drop result

Project
Circuit
Prepared by
Revision
System / source
AC single-phase · 120 V
Load
15 amps · 15 A calculated
Run length
100 ft one way
Conductor
12 AWG Copper
Parallel conductors
1 per phase
Power factor / reactance
0.9 · 0.08 mΩ/m
Conductor temperature
75°C
Maximum target
3%

Calculated decision

Voltage lost
5.63 V
Calculated drop
4.69%
Estimated load voltage
114.37 V
Target status
REVISE
Maximum one-way length
63.96 ft
Recommended size
10 AWG
Project and report information

Circuit inputs

Circuit and load

Calculated load current15 A
Advanced conductor and AC assumptions

The reactance presets are sensitivity scenarios, not installation-specific guarantees. Use manufacturer or project impedance data when available. Parallel conductors are modeled as identical, equal-length paths sharing current equally.

Circuit preview

Source-to-load voltage

Source120 V
100 ft one wayCopper 12 AWG
Estimated load114.37 V

Calculated result

Voltage-drop details

Voltage lost5.63 V
Percentage drop4.69%
Estimated load voltage114.37 V
Selected target3% — REVISE
Minimum size from voltage-drop model10 AWG

Smallest modeled size meeting the selected drop target with the entered circuit assumptions.

Maximum one-way length with selected size63.96 ft

Approximate maximum length before the selected drop target is exceeded.

Nearby conductor comparison

Comparison uses the first run's length and the same material, load, temperature, parallel-path, and impedance assumptions.

SizeDropLoad voltageTarget
14 AWG7.44%111.07 VREVISE
12 AWG4.69%114.37 VREVISE
10 AWG2.96%116.45 VPASS
8 AWG1.87%117.75 VPASS
6 AWG1.19%118.58 VPASS

Governing calculation

2 × current × one-way length × effective impedance

75°C effective resistance
6.8001 Ω/km
Effective modeled impedance
6.155 Ω/km
Circuit multiplier
2
Parallel conductors
1 per phase/polarity
Voltage drop is only one conductor-sizing check

The recommended size is based only on this voltage-drop model. It does not verify ampacity, continuous-load sizing, temperature correction, conductor count, terminal ratings, overcurrent protection, fault current, or local code requirements. The final conductor must satisfy every applicable requirement.

Report and share

Export this voltage-drop calculation

The PDF and CSV include circuit inputs, conductor comparison, formulas, coordinated ampacity context, and project information.

Continue this calculation

Send these inputs to another calculator

The destination opens with compatible conduit and cable inputs already selected. This calculator and its results remain unchanged.

Calculation guidance

Use the result as one part of conductor selection

Enter the one-way source-to-load distance. The calculator defaults to conductor resistance at 75°C and, for AC circuits, combines resistance and reactance using the entered power factor. Temperature and parallel-path assumptions are available under Advanced options. Review the complete formulas and source notes on the methodology page.

Voltage-drop FAQ

Common calculation questions

Should I enter one-way length or total circuit length?

Enter the one-way distance from the source to the load. The calculator applies the return-path factor for DC two-wire and single-phase circuits, or the square-root-of-three factor for balanced three-phase circuits.

Does the recommended conductor size verify ampacity?

No. It is the smallest modeled conductor that meets the selected voltage-drop target only. Ampacity, continuous-load sizing, temperature correction, conductor count, terminal ratings, overcurrent protection, fault current, and local requirements must be checked separately.

Why are power factor and reactance included?

AC voltage drop depends on both resistance and reactance. Power factor changes how those components contribute. The advanced inputs let you replace the planning assumptions when project-specific impedance data is available.

Is 3% voltage drop a mandatory limit?

Not universally. Three percent is a common design target, and NEC informational notes discuss 3% branch-circuit and 5% combined feeder-plus-branch performance. Informational notes are explanatory, so confirm the adopted code, project criteria, and equipment requirements.

Can I save or share the calculation?

Yes. Print a branded report or save it as PDF, download a branded CSV, or copy a URL that restores the calculator inputs.

Can I calculate a feeder and branch circuit together?

Yes. Select Feeder plus branch circuit, then enter each segment's one-way length and conductor size. The calculator shows the feeder drop, branch drop, combined drop, and estimated voltage at the final load.

Can I enter watts, kilowatts, VA, or kVA?

Yes. Choose the load unit and the calculator converts the entered load to current using circuit voltage, phase, and power factor as applicable. The derived amperes remain visible beside the inputs.