Base table size
12 AWGCopper EGC for an overcurrent device not exceeding 20 A.
Size a wire-type equipment grounding conductor from the overcurrent device and proportionally adjust it when phase conductors are increased.
This calculator addresses one wire-type EGC in one non-parallel raceway through 600 A. Verify the adopted code, effective ground-fault-current path, wiring method, material restrictions, special equipment rules, taps, motors, and AHJ requirements.
Calculation inputs
Transparent calculation
Copper EGC for an overcurrent device not exceeding 20 A.
12 AWG installed area ÷ 12 AWG minimum area.
6,530 cmil × 1.
Next supported conductor area meeting or exceeding the calculated requirement.
Continue this calculation
The destination opens with compatible conduit and cable inputs already selected. This calculator and its results remain unchanged.
Method and scope
The result reproduces the supported portion of 2023 NEC Table 250.122 and applies proportional circular-mil adjustment when the installed phase conductor is larger than the entered minimum.
Required verification
It does not determine the overcurrent device, phase-conductor ampacity, raceway-as-EGC suitability, fault-current performance, parallel-raceway rules, motor or tap provisions, material installation restrictions, or final code compliance.