Base table size
12 AWGCopper EGC for an overcurrent device not exceeding 20 A.
Size a wire-type equipment grounding conductor and apply proportional adjustment when phase conductors are increased. New here? Read the quick guide.
Report details
This calculator addresses one wire-type EGC in one non-parallel raceway through 600 A. Verify the adopted code, effective ground-fault-current path, wiring method, material restrictions, special equipment rules, taps, motors, and AHJ requirements.
Calculation inputs
Transparent calculation
Transfers 3 × 12 AWG Copper phase conductors and 1 × 12 AWG Copper equipment grounding conductor.
Copper EGC for an overcurrent device not exceeding 20 A.
12 AWG installed area ÷ 12 AWG minimum area.
6,530 cmil × 1.
Next supported conductor area meeting or exceeding the calculated requirement.
Report and share
The PDF and CSV retain the base table size, proportional adjustment, final standard size, and project context.
Continue this calculation
The destination opens with compatible conduit and cable inputs already selected. This calculator and its results remain unchanged.
Method and scope
The result reproduces the supported portion of 2023 NEC Table 250.122 and applies proportional circular-mil adjustment when the installed phase conductor is larger than the entered minimum.
Required verification
It does not determine the overcurrent device, phase-conductor ampacity, raceway-as-EGC suitability, fault-current performance, parallel-raceway rules, motor or tap provisions, material installation restrictions, or final code compliance.