Equipment Grounding Conductor Calculator

Equipment Grounding Conductor Calculator
Calculators

Size a wire-type equipment grounding conductor and apply proportional adjustment when phase conductors are increased. New here? Read the quick guide.

Report details

Grounding inputs and sizing result

Project
Circuit
Prepared by
Revision
Protective device
20 A
Phase conductors
3 × 12 AWG Copper · stranded
Minimum phase size
12 AWG
EGC material / construction
Copper · stranded

Calculated decision

Base table EGC
12 AWG
Phase-area ratio
× 1
Required EGC area
6,530 cmil
Final wire-type EGC
12 AWG Copper
2023 NEC reference — narrow planning scope

This calculator addresses one wire-type EGC in one non-parallel raceway through 600 A. Verify the adopted code, effective ground-fault-current path, wiring method, material restrictions, special equipment rules, taps, motors, and AHJ requirements.

Calculation inputs

Circuit protection

Project information for worksheet

Transparent calculation

How the grounding size was selected

Use both conductor rows in Conduit Size

Transfers 3 × 12 AWG Copper phase conductors and 1 × 12 AWG Copper equipment grounding conductor.

Continue to Conduit Size
1

Base table size

12 AWG

Copper EGC for an overcurrent device not exceeding 20 A.

2

Phase-conductor increase

× 1

12 AWG installed area ÷ 12 AWG minimum area.

3

Required EGC area

6,530 cmil

6,530 cmil × 1.

4

Final standard size

12 AWG

Next supported conductor area meeting or exceeding the calculated requirement.

Report and share

Export this grounding calculation

The PDF and CSV retain the base table size, proportional adjustment, final standard size, and project context.

Continue this calculation

Send these inputs to another calculator

The destination opens with compatible conduit and cable inputs already selected. This calculator and its results remain unchanged.

Method and scope

What this result establishes

The result reproduces the supported portion of 2023 NEC Table 250.122 and applies proportional circular-mil adjustment when the installed phase conductor is larger than the entered minimum.

Required verification

What remains outside this calculator

It does not determine the overcurrent device, phase-conductor ampacity, raceway-as-EGC suitability, fault-current performance, parallel-raceway rules, motor or tap provisions, material installation restrictions, or final code compliance.