Size a wire-type equipment grounding conductor from the overcurrent device and proportionally adjust it when phase conductors are increased.

2023 NEC reference — narrow planning scope

This calculator addresses one wire-type EGC in one non-parallel raceway through 600 A. Verify the adopted code, effective ground-fault-current path, wiring method, material restrictions, special equipment rules, taps, motors, and AHJ requirements.

Calculation inputs

Circuit and conductor sizes

Project information for worksheet

Transparent calculation

How the grounding size was selected

1

Base table size

12 AWG

Copper EGC for an overcurrent device not exceeding 20 A.

2

Phase-conductor increase

× 1

12 AWG installed area ÷ 12 AWG minimum area.

3

Required EGC area

6,530 cmil

6,530 cmil × 1.

4

Final standard size

12 AWG

Next supported conductor area meeting or exceeding the calculated requirement.

Continue this calculation

Send these inputs to another calculator

The destination opens with compatible conduit and cable inputs already selected. This calculator and its results remain unchanged.

Method and scope

What this result establishes

The result reproduces the supported portion of 2023 NEC Table 250.122 and applies proportional circular-mil adjustment when the installed phase conductor is larger than the entered minimum.

Required verification

What remains outside this calculator

It does not determine the overcurrent device, phase-conductor ampacity, raceway-as-EGC suitability, fault-current performance, parallel-raceway rules, motor or tap provisions, material installation restrictions, or final code compliance.