Branch Circuit Wire Size Calculator

Branch Circuit Wire Size Calculator
Calculators

Coordinate ampacity, voltage drop, protective-device review, and equipment grounding in one workflow. New here? Read the quick guide.

Project details (optional)Add details

Report details

Circuit inputs and coordinated result

Project
Location
Prepared by
System
Single-phase AC
Source voltage
120 V
Loads
0 A continuous + 16 A noncontinuous
Conductor
Copper · stranded
Insulation / terminals
90°C (194°F) / 75°C (167°F)
Ambient / CCC
30°C (86°F) · 2 current-carrying
Run / target
100 ft · 3% maximum
Power factor / reactance
1 · 0.08 mΩ/m
Protective device
20 A confirmed

Calculated decision

Required ampacity
16 A
Ampacity minimum
12 AWG
Voltage-drop minimum
8 AWG
Final phase conductor
8 AWG Copper
Calculated voltage drop
2.62 V · 2.19%
Wire-type EGC
8 AWG Copper
Governing check
Voltage drop governs
Planning status
PASS
Supported planning scope

For common DC, single-phase, and balanced three-phase circuits using one non-parallel conductor per phase. The calculator does not model neutrals, motors, HVAC, welders, EV-specific rules, taps, dwelling allowances, hazardous locations, or local amendments.

Guided circuit inputs

Circuit load

Coordinated result

How the final size was selected

Use this conductor plan in Conduit Size

Transfers 2 × 8 AWG Copper circuit conductors and 1 × 8 AWG Copper equipment grounding conductor.

Continue to Conduit Size
1

Load requirement

16 A

16 A + 125% × 0 A.

2

Ampacity minimum

12 AWG

20 A planning limit after the entered conditions.

3

Voltage-drop minimum

8 AWG

First supported size at or below the 3% target.

4

Final coordinated size

8 AWG

Voltage drop governs; calculated drop 2.19%.

Protective-device review: planning checks pass

20 A device · required load ampacity 16 A · final conductor planning limit 50 A.

Report and share

Export this coordinated circuit plan

The report retains ampacity, voltage-drop, protective-device, grounding, and governing-size calculations.

Continue this calculation

Send these inputs to another calculator

The destination opens with compatible conduit and cable inputs already selected. This calculator and its results remain unchanged.

What this coordinates

One visible planning sequence

The result reuses the site’s ampacity, voltage-drop, and equipment-grounding engines. The larger of the ampacity and voltage-drop sizes becomes the installed circuit conductor, then the entered protective device and any phase-conductor increase are applied to the wire-type EGC.

What you must verify

No hidden installation assumptions

Confirm the protective device, neutral treatment, conductor count, wiring method, exact conductor product, raceway, local amendments, equipment instructions, and authority-having-jurisdiction requirements before installation.