Coordinate 2023 NEC ampacity planning, voltage drop, a user-confirmed protective device, wire-type equipment grounding, and an exact-product conduit-sizing handoff.

Supported planning scope

For common DC, single-phase, and balanced three-phase circuits using one non-parallel conductor per phase. The calculator does not model neutrals, motors, HVAC, welders, EV-specific rules, taps, dwelling allowances, hazardous locations, or local amendments.

Guided circuit inputs

Load and installation conditions

Coordinated result

How the final size was selected

1

Load requirement

16 A

16 A + 125% × 0 A.

2

Ampacity minimum

12 AWG

20 A planning limit after the entered conditions.

3

Voltage-drop minimum

8 AWG

First supported size at or below the 3% target.

4

Final coordinated size

8 AWG

Voltage drop governs; calculated drop 2.19%.

Protective-device review: planning checks pass

20 A device · required load ampacity 16 A · final conductor planning limit 50 A.

Continue this calculation

Send these inputs to another calculator

The destination opens with compatible conduit and cable inputs already selected. This calculator and its results remain unchanged.

What this coordinates

One visible planning sequence

The result reuses the site’s ampacity, voltage-drop, and equipment-grounding engines. The larger of the ampacity and voltage-drop sizes becomes the installed circuit conductor, then the entered protective device and any phase-conductor increase are applied to the wire-type EGC.

What you must verify

No hidden installation assumptions

Confirm the protective device, neutral treatment, conductor count, wiring method, exact conductor product, raceway, local amendments, equipment instructions, and authority-having-jurisdiction requirements before installation.