Load requirement
16 A16 A + 125% × 0 A.
Coordinate 2023 NEC ampacity planning, voltage drop, a user-confirmed protective device, wire-type equipment grounding, and an exact-product conduit-sizing handoff.
For common DC, single-phase, and balanced three-phase circuits using one non-parallel conductor per phase. The calculator does not model neutrals, motors, HVAC, welders, EV-specific rules, taps, dwelling allowances, hazardous locations, or local amendments.
Guided circuit inputs
Coordinated result
16 A + 125% × 0 A.
20 A planning limit after the entered conditions.
First supported size at or below the 3% target.
Voltage drop governs; calculated drop 2.19%.
20 A device · required load ampacity 16 A · final conductor planning limit 50 A.
Continue this calculation
The destination opens with compatible conduit and cable inputs already selected. This calculator and its results remain unchanged.
What this coordinates
The result reuses the site’s ampacity, voltage-drop, and equipment-grounding engines. The larger of the ampacity and voltage-drop sizes becomes the installed circuit conductor, then the entered protective device and any phase-conductor increase are applied to the wire-type EGC.
What you must verify
Confirm the protective device, neutral treatment, conductor count, wiring method, exact conductor product, raceway, local amendments, equipment instructions, and authority-having-jurisdiction requirements before installation.